Alstom Cuts Natural Gas Use in London Train Depots by 37%

Alstom reported substantial natural gas savings at two London Underground maintenance depots after installing a simple, hardwired control that links depot doors to heating systems. The company measured a 37% reduction at Morden and a 33% reduction at Golders Green during recent winter periods, and it plans to roll the system out to other UK depots.

How the door-heater interlock stops heat loss the moment doors open

The solution uses a fixed, wired interlock between large bay doors and the depot’s heating plant so that when a door begins to open the heating automatically shuts off and remains off until the door is fully closed. Technicians added a controlled override so staff can keep heat on when operational needs require it. In practice, this prevents the heating from pumping energy into the building during the exact minutes when warm air would spill outside, cutting waste at source rather than trying to recover lost heat later.

Measured savings and the data behind the headline percentages

Alstom compared winter consumption against a 2022/23 baseline. At Golders Green, natural gas usage dropped about 30% in winter 2024/25 and 33% in winter 2025/26 after the interlock went live in early 2024. At Morden, where the system was installed in 2025, gas use fell from 1.99 GWh in the 2022/23 reference winter to 1.26 GWh in the first monitored winter — a ~37% cut. Combined across the two depots for the evaluation periods, gas consumption ran roughly 3.24 GWh below the comparable 2022/23 levels, equating to roughly 657 tons of CO2e avoided based on the company’s emission factors.

Why the approach works especially well in long, high-volume maintenance sheds

Maintenance depots often measure hundreds of meters in length, with high ceilings and multiple tracks. Those architectural characteristics amplify convective and advective heat loss when large doors cycle frequently during operations. By eliminating heating output exactly when doors are open — rather than relying on thermostats or schedule-based controls that cannot detect door position — energy input matches effective retention windows. That behavioral alignment between heat generation and actual containment reduces wasted fuel without major building works.

Practical steps Alstom followed to implement the interlock at depots

Alstom’s field deployment followed a clear sequence that other operators can replicate:

1) Survey and door mapping: measure door sizes, cycle frequency, and door-open duration during representative winter operations to quantify potential exposure.

2) Control design: specify a robust, fail-safe hardwired interlock that signals the heating plant to go inactive when any mapped door opens and to resume when all doors report closed.

3) Operations integration: develop an override mode and train depot teams on when to use it (for example, when long dwell times inside the shed require continuous heat for personnel comfort or equipment protection).

4) Metering and baseline comparison: install or verify meters on gas feeds, select a historical baseline winter, and collect continuous data for at least one subsequent winter to validate savings.

5) Rollout plan: prioritize other depots by similar door geometry and operational patterns, implement pilot installations, and monitor differences across site types.

Examples and expected outcomes for different depot sizes

Small single-bay depots with infrequent door cycles will see modest gains because door-open losses form a smaller share of total heating loss. Medium depots with multiple daily movements typically see double-digit percentage reductions after interlock installation. Very long, multi-bay sheds like Golders Green and Morden — where door activity and internal volume both drive high hourly heating demand — realize the largest absolute and relative cuts, as Alstom’s 30–37% results show.

Operational trade-offs and risk controls to preserve safety and uptime

The system design must respect essential safety and maintenance functions. Alstom included a controlled override so staff can keep heating enabled during certain tasks. The interlock wiring should be fail-safe: a loss of the interlock should default to a safe heating state or alert operators depending on the site’s heating architecture and health-and-safety rules. Commissioning must verify that the control does not interfere with emergency door operation or fire systems.

Carbon and energy impact in fleet maintenance contexts

Alstom quantified depot-level impact and linked it to carbon savings: the 3.24 GWh avoided equals roughly 657 tonnes CO2e for the two depots over the monitored periods. For operators maintaining fleets of tens or hundreds of units, small percentage improvements in depot energy intensity compound over multiple facilities and years, lowering scope 1 emissions and reducing operational cost exposure to gas price volatility.

How Alstom plans to scale the measure across its UK estate

Following the two-depot pilots, Alstom intends to install the control at Wembley Depot by the end of 2026 and add further sites in 2027, with energy performance monitored across operating scenarios. This phased approach lets the team refine override rules and commissioning procedures to match different building geometries and operating rhythms.

What depot operators should test before committing

Operators should model payback using site-specific door-cycle data and gas tariffs, validate that internal controls integrate with existing building management systems (or can safely operate independently), and pilot the hardwired interlock during a winter season to collect empirical meter data rather than rely solely on simulation. Combining the control with other low-cost measures — better door seals, targeted air curtains at high-use entrances, and staff procedures that minimize unnecessary door openings — can further improve outcomes.

Bottom-line: targeted control, rapid results, low disruption

The door-heater interlock presents a low-infrastructure, quick-to-deploy intervention that aligns heating supply with containment conditions. Alstom’s field measurements (up to 37% gas savings at Morden and 33% at Golders Green) demonstrate that relatively modest engineering and operational changes can produce material energy and carbon reductions in depot environments without major retrofit works.